YVV-U,YVV-R,NYY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • Filler.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-16000001 3x16+10 21.5 970 1000 98 80
28-16000002 3x25+16 25.0 1400 1000 0.7270 128 106
28-16000003 3x35+16 27.0 1750 1000 0.5240 157 131
28-16000004 3x50+25 31.0 2400 1000 0.3870 185 159
28-16000005 3x70+35 35.0 3300 1000 0.2680 228 202
28-16000006 3x95+50 40.0 4400 1000 0.1930 275 244
28-16000007 3x120+70 44.5 5550 500 0.1530 313 282
28-16000008 3x150+70 48.0 6550 500 0.1240 353 324
28-16000009 3x185+95 53.0 8200 500 0.0991 399 371
28-16000010 3x240+120 60.5 10600 500 0.0754 464 436

Technical Info

Catalog Info